Installation
1. Install valve on return line of equipment to be balanced or as
shown on the plans.
2. For maximum accuracy, the flow measurement/balancing
valve should be located in an unrestricted straight pipe run
so that no fittings (elbow, valve, tee, etc.) is closer to the
flow measurement/balancing valve than 5 pipe diameters
upstream and 2 pipe diameter downstream. If a balancing
valve is located downstream from a circulation pump, allow a
distance of ten (10) diameters between the pump and balanc-
ing valves.
3. Series CSM-81-F flow measurement/balancing valves are
bidirectional and should be installed to insure ease of hooking
up meter and adjusting setting
Flow Measurement Instruction
1. With wrench, turn indicator to open position on indicator
plate.
2. Connect, vent and prepare the differential gauge. Refer to
instructions furnished with the gauge.
3. After initial pressure differential reading is taken, refer to flow
rate charts to obtain flow rate based on pressure differential
and valve setting. If flow rate is in excess of that specified,
turn indicator towards closed position, noting pressure drop
and valve setting and determining new flow rates from flow
rate chart. The unit or system has now been balanced.
4. Disconnect differential gauge.
Watts Series CSM-81-F
Flow Measurement/Balancing Valves
Sizes: 2
1
2", 3", 4", 5", 6" and 8" (65, 80, 100, 125, 150, 200mm)
Installation Instructions
CSM-81-F
IS-CSM-81-F
The Watts Series CSM-81-F Flow Measurement/Balancing Valves are lubricated plug
valves designed for applications requiring balancing on medium to large flow rates. The
valve flanges are in accordance with ANSI B16.1 Class 125. Face to Face dimensions
are in accordance with ANSI B16.10.
Dimensions
Q - Typ.
‘S’ places
equally spaced
on bolt circle -
both flanges
K
Max. Screw Length
C
D
B
A
F
A1
1”
MODEL NO.
ORDERING
SIZE (DN) DIMENSIONS WEIGHT
Code A A1 B C D F K Q S
Face to Bolt Flange
Center to Center to
Flange Square Dia. of Screw No.of
Face Circle Dia. Top Bottom
Thickness
Stem Holes Length Holes
in. mm in. mm in. mm in. mm in. mm in. mm. in. mm in. mm in. mm in. mm lbs. kgs.
CSM-81-F 036540 2
1
2 65 7
1
2 191 5
1
2 140 7 178 5
1
8 130 3
15
16 99
11
16 17 1
1
4 31
3
4 19 2
1
2 64 4 29.5 13
CSM-81-F 036541 3 80 8 203 6 152 7
1
2 191 5
7
16 137 4
3
16 106
3
4 19 1
1
4 31
3
4 19 2
1
2 64 4 39 18
CSM-81-F 036535 4 100 9 229 7
1
2 191 9 229 6
1
2 165 4
15
16 125
15
16 24 1
1
2 38
3
4 19 2
1
2 64 8 61.5 28
CSM-81-F 036542 5 125 10
1
2 267 8
1
2 216 10 254 7
3
4 197 6 153 1 25 2 51
7
8 22 3
5
8 92 8 88 40
CSM-81-F 036543 6 150 10
1
2 267 9
1
2 241 11 279 7
3
4 197 6 153 1 25 2 51
7
8 22 3
5
8 92 8 100 45
CSM-81-F 036544 8 200 11
1
2 292 11
3
4 299 13
1
2 343 9
3
16 233 6
1
2 165 1
1
8 29 2 51
7
8 22 3
5
8 92 8 172 78
Zobrazit stránku 0
1 2 3 4 5 6 7 8

Shrnutí obsahu

Strany 1 - Watts Series CSM-81-F

Installation1. Install valve on return line of equipment to be balanced or as shown on the plans.2. For maximum accuracy, the flow measurement/balan

Strany 2 - Flow (water)

21⁄2" (65mm) CSM-81-F Flow CurveDial SettingPressure DifferentialPressure DifferentialFlow (water)feet*(water)160.080.040.020.010.05.04.02.01.0in

Strany 3 - 3” (75mm) CSM-81-F Flow Curve

3” (75mm) CSM-81-F Flow Curve* To convert to kg/m2, multiply feet of water by 304.8* To convert to psi, multiply feet of water by .43353Dial SettingPr

Strany 4

4” (100mm) CSM-81-F Flow CurveDial SettingPressure DifferentialPressure DifferentialFlow (water)feet*(water)160.080.040.020.010.05.04.02.01.0inches b

Strany 5

5” (125mm) CSM-81-F Flow CurveDial SettingPressure DifferentialPressure DifferentialFlow (water)feet*(water)160.080.040.020.010.05.04.02.01.0inches b

Strany 6

6” (150mm) CSM-81-F Flow CurveDial SettingPressure DifferentialPressure DifferentialFlow (water)feet*(water)160.080.040.020.010.05.04.02.01.0inches b

Strany 7

8” (200mm) CSM-81-F Flow CurveDial SettingPressure DifferentialPressure DifferentialFlow (water)feet*(water)160.080.040.020.010.05.04.02.01.0inches b

Strany 8 - EDP# 1911333 © Watts, 2008

IS-CSM-81-F 0829 EDP# 1911333 © Watts, 2008USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.comCanada: 5435 North Service Rd., Burlin

Komentáře k této Příručce

Žádné komentáře